How to set up plus + and minus - speeds on the Altivar 312 (and Altivar 31) drives?

Issue:
Set up plus and minus speeds on the Altivar 31/312 drives.

Product Line:
ATV31 and ATV312

Environment:
All serial numbers for ATV31 and ATV312

Cause:
If using a momentary push button to increase/decrease speed

Resolution:
Set up the drive as follows:
Wire one side of the switch to the +24v terminal and the other side of the minus switch to a logic input (example LI5)
Wire one side of the switch to the +24v terminal and  the other side of the plus switch to a logic input (example LI6)
Then program the drive as follows:
CTL menu
LAC set to 2 or 3
RFC Ref 2 switching set to Ch2 active
FR2 Ref 2 channel set to UPdt + and - speed control.
FUn menu
UPd + /- speeds
USP= + speed input for LI5 or you can choose your logic input assignment.
dSP= - speed input for LI6 or you can choose your logic input assignment.

Note: Conflicting functions need to be de-activated.  Set PS2 = PS4 = JOG = SA2 =  nO

Schneider Electric Казахстан

How to set up plus + and minus - speeds on the Altivar 312 (and Altivar 31) drives?

Issue:
Set up plus and minus speeds on the Altivar 31/312 drives.

Product Line:
ATV31 and ATV312

Environment:
All serial numbers for ATV31 and ATV312

Cause:
If using a momentary push button to increase/decrease speed

Resolution:
Set up the drive as follows:
Wire one side of the switch to the +24v terminal and the other side of the minus switch to a logic input (example LI5)
Wire one side of the switch to the +24v terminal and  the other side of the plus switch to a logic input (example LI6) 
Then program the drive as follows:
CTL menu
LAC set to 2 or 3
RFC Ref 2 switching set to Ch2 active
FR2 Ref 2 channel set to UPdt + and - speed control.
FUn menu
UPd + /- speeds
USP= + speed input for LI5 or you can choose your logic input assignment.
dSP= - speed input for LI6 or you can choose your logic input assignment.

Note: Conflicting functions need to be de-activated.  Set PS2 = PS4 = JOG = SA2 =  nO

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.