Is there a way to check the power supply budget and consumption in Unity software?

Goals and Symptoms

Is there a way to check the power supply budget and consumption in Unity software?

Causes and Fixes

Yes, the procedure below can be used to see the power consumption on each rack for either Premium or Quantum PLCs.
In the configuration, go to the desired bus drop and right click on the power supply.
.140 CPU
Choose Power Supply and IO Budget, and you will get a screen like the one below:
.power supply
The colors describing the power consumption are as follows:
colors
When the power budget is exceeded you will see a display like this one:
.power supply 2