WebReporter Is Asking For Credentials Everytime A Report Is Run

Issue
Every time the customer runs a report he get ask for credentials no matter what user he is log in as

Product Line
ION 6.x
SPM 7.x

Environment
Web Reporter Login

Cause
Reporting services is setup to ask for permission each time.

Resolution
To correct this follow the following procedure:

- Open IE (Internet Explorer)
- go to //localhost/Reports_ION
- Click on ION Reports


- Click on IONReportDataSource




- Go to the Connect Using section, and select "Windows Integrated Security", and click on apply