{}

Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
Поиск часто задаваемых вопросов
How to setup and connect a 3720 ACM with ethernet option in ION Enterprise v6.0 Management Console.

1) Add a new ethernet device to the Management Console and add the group, name, device type, and IP Address like normal.
2) On the same ethernet device configuration page right click in the white area (below the description field) and select Advanced Properties.
3) Change the TCP/IP Port to 3720 ACM with MPE|3721 which should be an option in the drop down menu.
4) Click OK to finish


Date Created: November 20, 2009
Last Revised: November 24, 2009
Public
Original Author: LA
All content © 1992-2009 Schneider Electric


Legacy KB System (APS) Data: RESL200582 V1.0, Originally authored by MiNe on 11/24/2009, Last Edited by MiNe on 11/24/2009
Related ranges: 3720 ACM, ION Enterprise V6.0

Schneider Electric Казахстан

Узнайте больше
Линейка:
Статьи, которые могут оказаться полезными
Узнайте больше
Линейка: