{}

Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
Поиск часто задаваемых вопросов
What is the correct order to upgrade the exec in the Quantum Unity processor 140CPU651x0?

1. Processor Operating Systems are upward compatible: updating a processor with a higher Operating System version is always allowed

2. It is recommended to always upgrade the OS version of a processor with the latest available version

3. It is recommended that the Copro version is associated with the OS version indicated in the QUANTUM - Launch History tables (mandatory for HotStandby Systems)

4. It is mandatory to upgrade the Ethernet Coprocessor before the Processor OS

5. It is not recommended to downgrade the OS of a Processor


Schneider Electric Казахстан

Узнайте больше
Линейка:
Статьи, которые могут оказаться полезными
Узнайте больше
Линейка: