Поиск часто задаваемых вопросов
How to upload a pre configured CID/IID file to a MiCOM relay?
Issue
Cannot upload a pre configured CID/IID file to a MiCOM relay.
Product Line
MiCOM Relays
Environment
IEC61850 communications
Cause
MiCOM relays expects a MCL file for IEC61850 configuration settings.
Resolution
Unfortunately, a CID/IID file cannot be uploaded directly to a MiCOM relay. The CID/IID file needs to be converted into an MCL file before the configuration settings can be uploaded to the relay.
This can be done by following the below steps:
1. Depending on the version of IEC61850 edition being used select the appropriate configurator from Tools.
![IED Configurator IED Configurator](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000008zqK9QAI&oid=00DA0000000abSm)
2. Once the configurator is open, go to File--> Import SCL
![Import SCL Import SCL](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000008zqP3QAI&oid=00DA0000000abSm)
3. Select the appropriate SCD/CID/IID file that needs to be converted.
![Select format Select format](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000008zqP8QAI&oid=00DA0000000abSm)
4. Open the SCD/CID/IID and then go to File--> Save.
![Open file Open file](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000008zqM5QAI&oid=00DA0000000abSm)
Cannot upload a pre configured CID/IID file to a MiCOM relay.
Product Line
MiCOM Relays
Environment
IEC61850 communications
Cause
MiCOM relays expects a MCL file for IEC61850 configuration settings.
Resolution
Unfortunately, a CID/IID file cannot be uploaded directly to a MiCOM relay. The CID/IID file needs to be converted into an MCL file before the configuration settings can be uploaded to the relay.
This can be done by following the below steps:
1. Depending on the version of IEC61850 edition being used select the appropriate configurator from Tools.
2. Once the configurator is open, go to File--> Import SCL
3. Select the appropriate SCD/CID/IID file that needs to be converted.
4. Open the SCD/CID/IID and then go to File--> Save.