What does the RDY status mean on the ATV61 and ATV71 drives?
Issue:
RDY status meaning on the ATV61 and ATV71 drives.

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Drive will be running for minutes then go back to RDY mode

Resolution:
RDY means the drive is waiting to get a run command in order to run.  Please check your command type in menu 1.6 or look at the HMI to see if the command type is terminal, HMI or NET.
In 2 wire control, you will need to maintain a constant +24vdc on the LI1 to make the drive run forward.
In 3 wire control, you will need to have your NC stop wired into LI1 and your NO start wired into LI2.   If the drive is running and you open NC stop then the drive will go back to RDY.

Schneider Electric Казахстан

What does the RDY status mean on the ATV61 and ATV71 drives?
Issue:
RDY status meaning on the ATV61 and ATV71 drives.

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Drive will be running for minutes then go back to RDY mode

Resolution:
RDY means the drive is waiting to get a run command in order to run.  Please check your command type in menu 1.6 or look at the HMI to see if the command type is terminal, HMI or NET.
In 2 wire control, you will need to maintain a constant +24vdc on the LI1 to make the drive run forward.
In 3 wire control, you will need to have your NC stop wired into LI1 and your NO start wired into LI2.   If the drive is running and you open NC stop then the drive will go back to RDY.
 

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.