{}

Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.

Поиск часто задаваемых вопросов

Video: How to set Password on an InRow ACRD200 cooling unit

Issue:
How set Password on an ACRD200 cooling unit

Product line:
InRow ACRD200

Environment:
All Serial Numbers

Cause:
Install, Configuration

Resolution:


Press ESC until you get to the main screen (On/Standby)

Use the Up or Down arrows to find the heading Set Password

Press ENTER and select Time

Now you will be prompted for a password

Use the default password of “apc”

If this does not work check with your Admin for the correct password

If password has been lost use the last eight digits of the serial number

Press Enter again and select the Password you would like to change, either Admin or Device.

Enter new password and press ENTER.

In the next screen, select an amount of minutes for Password time out, it can be any value between 1 and 10 minutes. Once you do this, press ENTER again to accept the changes.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка: