Issue:
Does OFS recognize the bit rank of a DDT (Derive Data Type)?
Product Line:
OPC Factory Server
Resolution:
OFS does not support bit ranks of a DDT. Unity is not able to export the overloaded comments of DDT members instance (bit rank). It was to make the data dictionary as light as possible.
Two possible workaround :
- access the extracted bit via the complete syntax ddt_inst.int.bit
- move the Bit rank to a Bool variable
Does OFS recognize the bit rank of a DDT (Derive Data Type)?
Product Line:
OPC Factory Server
Resolution:
OFS does not support bit ranks of a DDT. Unity is not able to export the overloaded comments of DDT members instance (bit rank). It was to make the data dictionary as light as possible.
Two possible workaround :
- access the extracted bit via the complete syntax ddt_inst.int.bit
- move the Bit rank to a Bool variable
Опубликовано для:Schneider Electric Казахстан

