Does 140NOE77110 work with 140CPU67160
Question:
Does 140NOE77110 work with 140CPU67160 as we found it not able to configure(grey out) in UP11?

Answer:
140NOE77110 works with 140CPU67160 in hardware perspective.
UP11 masks this selection since 140NOE77110 is obsolete & 140NOE77111 is the alternative module.
If customer uses UP3.0, he could configure the 140NOE77110 with 140CPU67160.

Schneider Electric Казахстан

Does 140NOE77110 work with 140CPU67160
Question:
Does 140NOE77110 work with 140CPU67160 as we found it not able to configure(grey out) in UP11?
 
Answer:
140NOE77110 works with 140CPU67160 in hardware perspective.
UP11 masks this selection since 140NOE77110 is obsolete & 140NOE77111 is the alternative module.
If customer uses UP3.0, he could configure the 140NOE77110 with 140CPU67160.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.