{}

Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.

Поиск часто задаваемых вопросов

How to save the parameters in the keypad and upload to another identical ATV630 drive.

Article available in these languages: Нидерландский

Issue:
Trying to save the parameters in the keypad and upload them to another identical ATV630 drive.

Product Line:
ATV630 drives

Environment:
Keypad

Cause:
Transferring files

Resolution:
Go to Main menu and scroll down to menu 7: File Management and press Ok.
Select 7.1-Transfer config file- select copy from the drive ( to save to the keypad) or select Copy to the drive (to upload the keypad setting to the drive).

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка: