Issue:
Cooling fans run adjustments on ATV630 and ATV930 Process Drives
Product Line:
Altivar ATV630 and ATV930
Environment:
All
Cause:
Wants to know when the fans run on the drive.
Resolution:
The fans for the drive up to 90kW can be run in 3 modes :
- Standard : at run order
- Always : the fans run permanently
- Economy : The fans run according to the drive thermal state
For the drives upper than 90kW, the fans run only at run order.