Why can I not set my transient percentage below 105 for my ION 7650 meter?

Issue:
A customer is configuring the transient power quality setting and wants to use a percentage lower than 105.

Product Line:
ION 7650 meters

Environment:
ION Setup

Cause:
This is a restriction that is hard coded into the ION Transient Module.

Setup Assistant Transient settings

Resolution:
The lowest value which can be selected is 105% percent and the upper limit is 1000%.

Schneider Electric Казахстан

Why can I not set my transient percentage below 105 for my ION 7650 meter?

Issue:
A customer is configuring the transient power quality setting and wants to use a percentage lower than 105.

Product Line:
ION 7650 meters

Environment:
ION Setup

Cause:
This is a restriction that is hard coded into the ION Transient Module.

Setup Assistant Transient settings 

Resolution:
The lowest value which can be selected is 105% percent and the upper limit is 1000%.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.