Video: How to configure the Function and Timing of "RENF22R2MMW NFC Timing Relay" product using smart phone?

Article available in these languages: Французский, Нидерландский

Step 1 : Product Identification
Step 1.1 Initiate the NFC App
Step 1.2 Select the Read button
Step 1.3 Place the phone in front of NFC Timing Relay. And adjust the phone until the “Pairing Indication LED” lit-up.
Step 1.4 Below screen appeared when Uploading is successfully executed.

Step 2 : Function & Timing selection
Step 2.1 Select the Function C, Off-delay relay with control signal.
Step 2.2 Timing selection, Press the T button and set T = 5s




Schneider Electric Казахстан

Вложения

Function & Timing Selection_Presentation.pdfFunction & Timing Selection_Presentation.pdf [603.96 KB]