Поиск часто задаваемых вопросов
How do you configure a relay output on ATV630/930 to indicate safety input status?
Issue:
The Altivar Process ATV630 and ATV930 needs a relay to indicate if the safety input is active or not active.
Product Line:
ATV630, ATV930
Environment:
All serial numbers, all model numbers
Cause:
Need for an indication of the safety circuit status on STOA / STOB input terminals.
Resolution:
Configure one of the relays of the drive to "Power Removal State":
Replace x with the number of the relay you want to use.
The Altivar Process ATV630 and ATV930 needs a relay to indicate if the safety input is active or not active.
Product Line:
ATV630, ATV930
Environment:
All serial numbers, all model numbers
Cause:
Need for an indication of the safety circuit status on STOA / STOB input terminals.
Resolution:
Configure one of the relays of the drive to "Power Removal State":
- Go to Complete Settings
- Go to Input/Output Relay
- Go to Rx Configuration
- Set Rx assignment to "Power Removal State"
Replace x with the number of the relay you want to use.
Опубликовано для:Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка: