Поиск часто задаваемых вопросов
How is imbalance factor calculated in EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420) for current imbalance protection
Imbalance factor for EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420) is calculated as follows:
Imbalance factor (%) = (Imax phase - Imin_phase) / Imax_phase x 100%
Imbalance factor (%) = (Imax phase - Imin_phase) / Imax_phase x 100%