Issue:
Needs to configure the ATV320 drive for more torque at low speeds.
Product Line:
Altivar 320
Environment:
All
Cause:
Wiring
Resolution:
Go to ConF > FULL > SEt > UFr to increase IR Compensation to 140, set Control Type to Standard.
Needs to configure the ATV320 drive for more torque at low speeds.