Can the AR8395 busbar install into a NetShelter SV? The busbar installs at three points, but the cabinet only has two accessory mounting brackets.
Issue:
The AR8395 busbar has three installation points.

Product Line:
NetShelter SV, AR8395

Environment:
All models, all serial numbers.

Cause:
NetShelter SV cabinets ship with two accessory mounting brackets.

Resolution:
The AR8395 busbar is compatible with NetShelter SV cabinets, but it does require an extra accessory bracket (AR824002).
See attached file.

Schneider Electric Казахстан

Вложения
20180716 AR8393 Installation into the NetShelter SV.pdf [31.78 KB]