What tightening torque has to be applied on the screws used for building the Prisma P enclosure framework?

Unless otherwise indicated in the instruction sheet delivered with the product, the tightening torque for the specific screw size indicated in the table below shall be applied


source: Prisma P catalog DESW016EN

The tightening torque to be applied on the screws of the Prisma P framework is listed in the table below: