Поиск часто задаваемых вопросов
Can the RM35JA31MW monitor positive and negative currents?
Issue:
Checking if Zelio relays can monitor negative currents.
Product line:
Relays and Timers
Environment:
Zelio Control and Measurement Relays
Cause:
Documentation shows on 4-20mA does not clarify positive or negative.
Resolution:
Yes, the RM35JA31MW can monitor +4 to +20mA or -4 to -20mA.
Checking if Zelio relays can monitor negative currents.
Product line:
Relays and Timers
Environment:
Zelio Control and Measurement Relays
Cause:
Documentation shows on 4-20mA does not clarify positive or negative.
Resolution:
Yes, the RM35JA31MW can monitor +4 to +20mA or -4 to -20mA.