Issue:
SOF fault on ATV320
Product Line:
Altivar Machine, ATV12
Environment:
All serial numbers
Cause:
• Instability
• Overspeed associated with the inertia of the application
Resolution:
• Check the motor
• Overspeed is 10% more than Maximum frequency tFr page 57 so adjust this parameter if necessary
• Add a braking resistor
• Check the size of the motor/drive/load
• Check parameters of the speed loop (gain and stability)
ATV user manual:
https://www.se.com/ww/en/download/document/BBV28581/