Поиск часто задаваемых вопросов
How to find PLC and Memory load of BMED581020 PLC (IEC 61499) by application
You must used “MIBGET” function block.
![mibget mibget](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V000009bGqfQAE&oid=00DA0000000abSmMAI)
Where is the list of “MIBGET” functionality?
![mibget list mibget list](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V000009bGqgQAE&oid=00DA0000000abSmMAI)
For CPU load:
![CPU load CPU load](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V000009bGqhQAE&oid=00DA0000000abSmMAI)
For Memory:
![memory load memory load](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V000009bGqiQAE&oid=00DA0000000abSmMAI)
Example of application with CPU load:![application mibget application mibget](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V000009bGqjQAE&oid=00DA0000000abSmMAI)
![mibget parameter mibget parameter](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V000009bGqpQAE&oid=00DA0000000abSmMAI)
![mibget parameter mibget parameter](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V000009bGqqQAE&oid=00DA0000000abSmMAI)
![mibget result mibget result](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V000009bGqrQAE&oid=00DA0000000abSmMAI)
Product line:
EAE, CPU load, Memory load, MIBGET, Simulator, BMED581020, IEC 61499
Environment:
Windows, EcoStruxure Automation Expert 22.0
Where is the list of “MIBGET” functionality?
For CPU load:
For Memory:
Example of application with CPU load:
- Add “MIBGET” function block like this
- Change parameter VALUE1 “STRING” to “UDINT” of “MIBGET” function block
- Save + Compile + deploy + RUN your application
- Generate event on REQ => result of value is 118 => CPU load = 11.8%
Product line:
EAE, CPU load, Memory load, MIBGET, Simulator, BMED581020, IEC 61499
Environment:
Windows, EcoStruxure Automation Expert 22.0
Опубликовано для:Schneider Electric Казахстан
Узнайте больше
Изделие:
Линейка:
Узнайте больше
Изделие:
Линейка: