undefined undefined
{}

Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
Чем мы можем помочь сегодня?
How can you setup a custom display to show temperature or pressure as the PID setpoint on the ATV212 Drives?

Issue:

Setting up custom display to show pressure or temperature values as the PID setpoint on the ATV212 Drives.

 

Product Line:

ATV212

 

Environment:

All

 

Cause:

Custom display

 

Resolution:

Example below will be to display 32F to 122F degrees temperature on the display as the PID setpoint.

Let's start with the Lowest value to set which is 32F.

 

32F divided by 1.5 (F702) = 21.3333

F706=21.33

 

Set now look at the Highest value to set which is 122F.

 

122F minus 32F= 90F minus F706 value of 21.33= 68.67

 

68.67X 1.5 (F702) =103.00+ F706 value 21.33= 124F Your highest value you can set. 

 

F701- 1 default.

F702= 1.5 

F703=1

F705=1

F706= 21.35

 

FNOD=3 PID keypad setpoint

F360= 1VIA

V380= PID inverse set to yes for temp PID

 

Now using up and down buttons your setpoint is between 32F and 124F. 

 

Note it will not show any units like F or Psi only the number.

 

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.