ATS480- How do you wire up 3-wire control on a ATS480 soft start?

Article available in these languages: Нидерландский

Issue:

Wiring a ATS480 for 3-wire control

 

Product Line:

ATS480

 

Environment:

All 

 

Cause:

Customer desires to wire in a momentary stop and start push button

 

Resolution:

Wire a normally closed stop pushbutton between the +24 and STOP terminals.

Wire a normally open start pushbutton between the +24 and RUN terminals.

When the soft start is part of an enclosed package or MCC package, then you need to look at the control wiring, for other wiring options.

 

3-wire control

The run and stop are controlled by 2 different logic inputs.

A stop is obtained by opening (state 0) the STOP input.

The pulse on the RUN input is set until the stop input opens.

On power-up or a manual fault reset or after a stop command, the motor can only be powered once the RUN

input has been opened (state 0) followed by a new pulse (state 1)

 

 

Also check with the customer in some cases they will wire the NC stop and NO Start in series with a relay coil and use a contact on the relay to latch the NO start to seal in the circuit.

They would then need to run the +24vdc through one of the no dry contacts on the seal relay, to close +24vdc and run-stop on the soft starter. If they use this type of external 3 wire 

control then they will need to wire the soft starter as 2 wire control by jumpering the run/stop together and switching 24vdc to run stop. 

 

 

Schneider Electric Казахстан

Было ли это полезно?

100% пользователей считают это полезным

Узнайте больше
Линейка:
Узнайте больше
Линейка:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.