PowerChute Network Shutdown ESXi host shutdown failed for vSAN standard cluster with Skip Maintenance mode enabled.
Issue:
ESXi host PowerChute Network Shutdown is running on failure to shutdown when configured for vSAN, and enabling Skip Maintenance mode has been selected.

Product:
PowerChute Network Shutdown version 5.x

Environment:
PowerChute deployed onto a vSAN datastore.
VMWare ESXi 7.x or 8.x

Cause:
The PowerChute shutdown delay is set to high.

Solution:
Edit the pcnsconfig.ini file and change the shutdown command duration to 0 (zero) seconds.

Default configuration
[Shutdown]
shutdownCommand =
shutdownCommandDuration = 60

After the change
[Shutdown]
shutdownCommand =
shutdownCommandDuration = 0

Schneider Electric Казахстан

PowerChute Network Shutdown ESXi host shutdown failed for vSAN standard cluster with Skip Maintenance mode enabled.
Issue:
 ESXi host PowerChute Network Shutdown is running on failure to shutdown when configured for vSAN, and enabling Skip Maintenance mode has been selected.

Product:
PowerChute Network Shutdown version 5.x

Environment:
PowerChute deployed onto a vSAN datastore.
VMWare ESXi 7.x or 8.x

Cause: 
The PowerChute shutdown delay is set to high.

Solution:
Edit the pcnsconfig.ini file and change the shutdown command duration to 0 (zero) seconds.

Default configuration
[Shutdown]
shutdownCommand = 
shutdownCommandDuration = 60 

After the change
[Shutdown]
shutdownCommand = 
shutdownCommandDuration = 0 

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Узнайте больше
Линейка:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.