{}

Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
Поиск часто задаваемых вопросов
How to read and modify variable by sending SMS to the Zelio Smart Module?
  1. In ZelioSoft:
When configuring the COM function block, select Variable modification as message Type:
Variable_modification

Regarding the Parameters, select people who are authorized to send Modification command and define the variable access to “Read and modification”:

Parameters
  1. Connection to the Zelio Smart module:
When connecting to the Zelio Smart module through the SR2COM01 the following popup window appears:
Write_options

From this window, define the access key which will be used in the command to read/modify variable(s). By default, it is 00000000.
  1. On Mobile phone:
To read the value of the variable which has the Alias B003, send the following command via SMS: 00000000!B003?

SMS1

To modify the value of the variable which has the Alias B003, send the following command via SMS: 00000000!B003=1
(In that case, the value '1' will be written in the variable having the Alias B003)

SMS2

If the variable and/or the recipient only have the read access, the following error should appear when trying to modify the value:

SMS3

Schneider Electric Казахстан

Узнайте больше
Изделие:
Линейка:
Статьи, которые могут оказаться полезными
Узнайте больше
Изделие:
Линейка: