- Increase the memory size in the Scadapack Workbench program.
- Under the program name in solution explorer, go to properties>Memory size, see details below.
Run the Memshow to check how many free NVram memory you have. - Connect to SCADAPack using SCADAPack E configurator
- Under Transfer menu, select Remote Command Line.
- Then Type command Memshow, it displays information related to system memory, see details below
Опубликовано для:Schneider Electric Казахстан
Discontinued
Discontinued
Discontinued
Discontinued
Discontinued
Discontinued