What is the standard lug size used in main breaker switchboards?

Issue:
What is the Standard lug size used for a main breaker QED SWBD?

Product Line:
QED Switchboards

Environment:
Products sold and used in the United States

Cause:
Conductor sizing

Resolution:
The lugs used for the main breaker lug pad will each accept (1) 3/0 to 750MCM cable as standard. Lug quantity is determined by amperage (335A per lug).