{}

Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Bienvenido(a) al sitio web para México de Schneider Electric

Te damos la bienvenida a nuestro sitio web para México.

Buscar Preguntas Frecuentes

Can Schneider Panelboards be built to meet seismic standards?

Issue:
What seismic standards are Schneider Panelboards be built to ?

Product Line:
NQ NF I-Line QMB Panelboards

Environment:
Seismic Zone Appllication

Resolution:
Square D NQ, NF, I-Line and QMB panelboards meet the seismic requirements of ICBO 2000 when the following guidelines are met:

Bolt-on circuit breakers are required on NQ and NF panelboards.
Boxes must be secured to wall/structure by utilizing all mounting holes provided in box and secured with grade 2 steel bolts sized per the mounting holes.

See Web link to Data Buletin, 1640DB0802.
"The seismic provisions of the 2006 International Building Code (IBC) requires strenuous shaker table testing for panelboards. The new NQ panelboard successfully completed this testing without any structural damage, while retaining electrical continuity."

https://www.se.com/us/en/download/document/1640DB0802/



Schneider Electric Mexico

Explora más
Rango:
Explora más
Rango: