Issue:
Conductors and wire sizes accepted by AF2320GETBMB and CF2530GETBMB
Product Line:
I Line II Busway
Environment:
Wire size accommodation for termination
Cause:
Clarification regarding the minimum and maximum wire size that can be run to terminate to theAF2320GETBMB and CF2530GETBMB end tap boxes
Resolution:
The 2000A End Cable Tap Box will accept (7) 1/0-600kcmil conductors per phase.
The 3000A End Cable Tap Box will accept (10) 1/0-600kcmil conductors per phase and neutral.
This and other Busway information can be found in the Busway Systems Class 5600 Catalog 5600CT9101