What is the highest ampacity Powerpact R-frame breaker that can be installed as an individually mounted main breaker in a QED-2 switchboard?
Issue:
Why can't I install a 3000 A R-frame breaker in my QED-2 switchboard?
Product line:
Main breaker switchboard sections
Environment:
QED-2 switchboards with main breakers
Resolutions:
The highest ampere R-frame that will install in a main section of a QED-2 switchboard is 2500 A. If 3000 A or higher is needed, you must use a Masterpact NW.
Why can't I install a 3000 A R-frame breaker in my QED-2 switchboard?
Product line:
Main breaker switchboard sections
Environment:
QED-2 switchboards with main breakers
Resolutions:
The highest ampere R-frame that will install in a main section of a QED-2 switchboard is 2500 A. If 3000 A or higher is needed, you must use a Masterpact NW.