Buscar Preguntas Frecuentes
Is there a difference in the P24 and +24 terminals on the ATV630 drives?
Issue:
Difference between the P24 and +24 terminals on the ATV630 drives.
Product Line:
ATV630
Environment:
All serial numbers
Cause:
N/A
Resolution:
P24 Output power supply for digital inputs and STO +24 Vdc Tolerance: –15...+20% Current: maximum 1.1 A
+24 Digital input power supply +24 Vdc input supply Tolerance: –15...+20% Current: 100 mA
Difference between the P24 and +24 terminals on the ATV630 drives.
Product Line:
ATV630
Environment:
All serial numbers
Cause:
N/A
Resolution:
P24 Output power supply for digital inputs and STO +24 Vdc Tolerance: –15...+20% Current: maximum 1.1 A
+24 Digital input power supply +24 Vdc input supply Tolerance: –15...+20% Current: 100 mA