{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Webreach Historical Data gives Pegquery error (80040c8e)

Symptom:
Vista queries work but the same query in Webreach returns:
------------------------------------------------
Webreach error:

"Pegquery error (80040c8e)"

"ActiveX component cannot create object"
"/ion/historical/getlogs.asp line 51"
-----------------------------------------------
This is often due to Vista inheritance issues. To fix:

1) Open Vista
2) Navigate to the Top level window (all the Vista diagrams are linked to each other with Parent-Child relationships)
3) Open the Toolbox and right click on the background
4) Under the Query Server tab select Edit Link> Choose Query1 (or any custom query server)
5) Click OK and save this

After completing the above simple procedure, webreach historical data for this query should work.

Schneider Electric Malaysia

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: