How do you reset the ATV61 and 71 VFD parameters to default factory settings?

Issue:
Can I reset the ATV61/71 drives parameters to default factory settings?

Product Line:
ATV61/71

Environment:
All range, All serial number

Cause:
Need to reset the ATV61/71 VFD parameters to factory setting?

Resolution:
To factory reset the VFD you must go to the Drive menu.

  1. Scroll to menu 1.12 Factory Setting and press enter
  2. Select Parameter group list – Select All and press enter
  3. Press Esc once
  4. Scroll to Factory setting and press enter
  5. Please check that wiring is ok and press enter
Factory reset is now done.