{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Video: How do I program and wire an ATV212 to run using 3-wire control?

Article available in these languages: Spanish

Issue:
Configuring Altivar 212 Drives for 3-Wire Control

Product Line:
Altivar Buildings 212

Cause:
Need to use 3-wire (momentary) control

Resolution:
Programming:
Press MODE key to AUF
Arrow down to F---, and  press ENT key
Set F111 to 2
Set F112 to 49

Wiring:
Wire the F terminal from a Normally Open (NO), momentary close, START contact
Wire the R terminal from a Normally Closed (NC), momentary open, STOP contact



If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Malaysia

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: