Follow below mentioned steps to configure different audible alarms as per alarm priorities.
1. In Citect Project editor open Computer setup editor > under Alarm group add sound<n> parameter. Browse and select the sound file (in .wav format) as per alarm priority. Add sound<n>Interval in Ctect.ini. Same way different sound files can be configured as per different alarm priorities.
2. Define alarm priority as per different alarm categories.
3. Then go to Citect project Editor > Systems > Included Projects and add CSV_Include project.
4. Run computer setup wizard and in the Events setup enable CSV_AlarmClient. Then complete the wizard and start runtime.
Released for: Schneider Electric Malaysia
Follow below mentioned steps to configure different audible alarms as per alarm priorities.
1. In Citect Project editor open Computer setup editor > under Alarm group add sound<n> parameter. Browse and select the sound file (in .wav format) as per alarm priority. Add sound<n>Interval in Ctect.ini. Same way different sound files can be configured as per different alarm priorities.
2. Define alarm priority as per different alarm categories.
3. Then go to Citect project Editor > Systems > Included Projects and add CSV_Include project.
4. Run computer setup wizard and in the Events setup enable CSV_AlarmClient. Then complete the wizard and start runtime.
Released for: Schneider Electric Malaysia








Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales enquiry online and an expert will connect with you.