{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

My Process Drive with Modbus serial is not indicating when my cable is disconnected or no Modbus communication?

Issue:
My Process Drive with  Modbus serial is not indicating when my cable is disconnected or no Modbus communication?

Product Line:
Altivar Machines

Environment:
All models and serial numbers

Cause:
Not default program to the drive.

Resolution:
Drive has to be configured for command and/or reference from Modbus or drive sees this as monitoring only, will not trip if it's not there.  Under Error/Warning Handling > Fieldbus Monitoring > SLL - Response to Modbus Interruption is set to Freewheel

Schneider Electric Malaysia

Explore more
Range:
Altivar Process ATV600Altivar Process ATV900
Explore more
Range:
Altivar Process ATV600Altivar Process ATV900
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.