Video: How do I setup a Read_Var in SoMachine Basic ?
Issue:
How do I setup a Read_Var in SoMachine Basic ?
Product Line:
M221
Enviroment:
ALL
Resolution:
Configure the Client IP Address![setup setup](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000009DZ8vQAG&oid=00DA0000000abSm)
Enter Server IP Address
![setup setup](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000009DZaEQAW&oid=00DA0000000abSm)
Create READ_VAR
![setup setup](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000009DZoEQAW&oid=00DA0000000abSm)
Enter Read_Var settings
![setup setup](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000009DZa9QAG&oid=00DA0000000abSm)
Enter Destination on Client (register to store Read on the Client)
![setup setup](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000009DZn8QAG&oid=00DA0000000abSm)
Set up Timer to Read once per second.
![timer timer](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000009DZYOQA4&oid=00DA0000000abSm)
How do I setup a Read_Var in SoMachine Basic ?
Product Line:
M221
Enviroment:
ALL
Resolution:
Configure the Client IP Address
- Select ETH1
- Enter IP Address, Subnet Mask and Gateway Address
Enter Server IP Address
- Select Modbus TCP
- Enter Server IP Address in IP Address Box
- Press Add Button
- Observe server IP Address and Index (Index will be used as ID in Read_Var)
Create READ_VAR
- Select Function Block
- Cursor down to Communications
- Select Read_Var
Enter Read_Var settings
- Change Link to ETH1
- Change ID to match Index from Configuration of ETH1 Modbus TCP
- Change FirstObj to 100 (This will be address to be read from Server)
- Enter Quantity of Addresses to be Read
Enter Destination on Client (register to store Read on the Client)
Set up Timer to Read once per second.