Issue:
Customer wants to read LED status on the ethernet switch using SNMP protocol.
Product Line:
Connexium Ethernet Switch TCSESM083F23F1
Environment:
Windows 7 Pro, iReasoning MIB browser
Resolution:
The very first step is to install the correct MIB file in the MIB Browser.
We need to install the two files in the MIB Browser.
1.SchneiderTFE-V03-00.mib
2.SchneiderElectricSwitches_V02_00.mib.
Contact your local country Schneider Electric Customer Care Center to get this files.
The LED status can for Power, Ring Manager, Standby, fault , Relay R1 and R2.
The OID for them are as below.
1. Power Supply P >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.1.0"
2. Fault >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.4.0"
3. Ring Manager RM >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.3.0"
4. Standby >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.2.0"
5. Relay R1 >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.5.0"
5. Relay R2 >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.6.0"
Customer wants to read LED status on the ethernet switch using SNMP protocol.
Product Line:
Connexium Ethernet Switch TCSESM083F23F1
Environment:
Windows 7 Pro, iReasoning MIB browser
Resolution:
The very first step is to install the correct MIB file in the MIB Browser.
We need to install the two files in the MIB Browser.
1.SchneiderTFE-V03-00.mib
2.SchneiderElectricSwitches_V02_00.mib.
Contact your local country Schneider Electric Customer Care Center to get this files.
The LED status can for Power, Ring Manager, Standby, fault , Relay R1 and R2.
The OID for them are as below.
1. Power Supply P >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.1.0"
2. Fault >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.4.0"
3. Ring Manager RM >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.3.0"
4. Standby >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.2.0"
5. Relay R1 >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.5.0"
5. Relay R2 >> oid=".1.3.6.1.4.1.3833.1.1.14.1.1.35.3.6.0"