What are the requirements of SEMI F47 that products tolerate in case of voltage sags?
SEMI F47 requires that products tolerate the following voltage sags:
- 50% remaining voltage, 50% missing voltage, for 200 milliseconds
- 70% remaining voltage, 30% missing voltage, for 500 milliseconds
- 80% remaining voltage, 20% missing voltage for one second.