Are there any system variables in Vijeo Designer to extract the Time of Day (TOD) clock from a Magelis/Harmony HMI?
Issue:
Are there any system variables in Vijeo Designer to extract the Time of Day (TOD) clock from a Magelis/Harmony HMI?

Product Line:
All Vijeo Designer HMIs

Environment:
TOD clock, system clock

Resolution:
Vijeo Designer does indeed have system variables for the TOD clock.
Below is a list of the system variables available:
_Hour
_Minutes
_Seconds
_Month
_Day
_DayoftheWeek (Sunday = 1, Monday =2, ...,  Saturday = 7)
_Year2 (last two digits of the current year)
_Year4 (all 4 digits of the current year

The data type of all of these values is "DINT".