{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
Veelgestelde vragen (FAQ's) zoeken
How can one program relays for ATV930 drive line?
Issue:
Program relays for the ATV930

Product Line:
Altivar 930

Environment:
All

Cause:
N/A

Resolution:
Under main menu, go into menu 5 complete settings.
Go into menu 5.11 Input/Output.
Go into the relay configuration tab.
Enter on each relay and change assignment as needed.

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Mogelijk nuttige artikelen
Ontdek meer
Productfamilie