Issue:
How do we export Alarm Group data from one project to another project in Vijeo Designer?

Product Line:
Vijeo Designer (all versions)

Resolution:
To export alarm group data from one project to another project in Vijeo Designer, follow this procedure:

1) Ensure both the new and old application have an alarm group with same name
2) In the old application, goto variables in the navigator window and right-click. Choose "Export Variables"
3) Save the variable csv file somewhere on your PC
4) On the new application, goto variables in the navigator window and right-click. Choose "Import Variables"
5) Find the csv file on your PC and press the open button.

This will bring your alarm data into the new project.