Does ATV600 have fire mode?
YEs, with fw 1.8 or newer there is forced mode function, configurable using parameters INH, INSH, INHR. Printscreen enclosed.
Desription of the function is mentioned in newest manual (ATV600_Programming_Manual_EN_EAV64318_05)