{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
Veelgestelde vragen (FAQ's) zoeken
How to roll back NetBotz firmware.
Issue:
How to roll back NetBotz firmware.

Product Line:
Netbotz

Environment:
NetBotz 3xx, 4xx, and 5xx firmware

Cause:
If for some reason you feel the need to revert back to a previous firmware (BotzWare) revision on a NetBotz appliance, you can not simply use the upgrade feature.


Resolution:
Follow the detailed instructions for the TFTP procedure highlighted in FA176133.

Replace step 1 with the version of BotzWare to which you are looking to downgrade. Older revisions may be available at: www.apc.com/tools/download

Please note that when downgrading, it is suggested that you not keep any of the old configuration and do not use the "rootupgkeep" option in step 17.

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Mogelijk nuttige artikelen
Ontdek meer
Productfamilie