{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
Veelgestelde vragen (FAQ's) zoeken
How to know the absence of x80 IO in local M580 rack when it is configured as Device DDT ?

1.Issue

How to know the absence of x80 IO in local M580 rack when it is configured as Device DDT ?

2.Environment

M580 series ,X80

3.Resolution

The detail diagnostics status of x80 IO could be accessed by implementing READ_STS_MX.
Here are two samples to get status for digital and analog modules.


When COM_FLT is set to 1 ,it means the module could not be detected by CPU and module would be absent in the rack.

Schneider Electric Netherlands

bijlage(n)
read_sts.zip [54.48 KB]
Ontdek meer
Productfamilie
Mogelijk nuttige artikelen
Ontdek meer
Productfamilie