ATV32, how can I configure an emergency stop that will still follow the deceleration ramp
Issue:
Configure an emergency stop that follows the dec ramp.

Product Line:
Altivar 32 series drives.

Environment:
All models, All serial numbers.

Cause:
An emergency stop function is needed that will still ramp the motor down. A freewheel emergency stop can not be used in this particular application, the motor must be ramped down and not allowed to freewheel.

Resolution:
Safe Stop 1 function can be used to initiate an emergency stop of the drive.  This can only be configured using SoMove.  The ramp-down time is defined by parameters SSrt and SSru.  Note that this input should be externally latched as the drive will be allowed to start again once the emergency stop signal on the terminal assigned to safe stop 1 is removed.

For more information, please refer to the ATV32 Safety Integrated Functions manual, document number S1A45606.

http://download.schneider-electric.com/files?p_Reference=S1A45606&p_EnDocType=User guide&p_File_Id=556547554&p_File_Name=ATV32_Safety_Functions_Manual_EN_S1A45606_05.pdf


Schneider Electric New Zealand

ATV32, how can I configure an emergency stop that will still follow the deceleration ramp
Issue:
Configure an emergency stop that follows the dec ramp.

Product Line:
Altivar 32 series drives.

Environment:
All models, All serial numbers.

Cause:
An emergency stop function is needed that will still ramp the motor down. A freewheel emergency stop can not be used in this particular application, the motor must be ramped down and not allowed to freewheel.

Resolution:
Safe Stop 1 function can be used to initiate an emergency stop of the drive.  This can only be configured using SoMove.  The ramp-down time is defined by parameters SSrt and SSru.  Note that this input should be externally latched as the drive will be allowed to start again once the emergency stop signal on the terminal assigned to safe stop 1 is removed.

For more information, please refer to the ATV32 Safety Integrated Functions manual, document number S1A45606.

http://download.schneider-electric.com/files?p_Reference=S1A45606&p_EnDocType=User guide&p_File_Id=556547554&p_File_Name=ATV32_Safety_Functions_Manual_EN_S1A45606_05.pdf


 

Schneider Electric New Zealand

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.