{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How to change the MAST task Cyclic to Periodic in RemoteConnect and SCADAPack x70 device?
In Cyclic mode, the MAST task uses all available time. Sufficient time should be allowed for bursts of other activity on the SCADAPack x70 device. For this reason, Cyclic mode is not recommended.

To change MAST task from Cyclic to Periodic:
  • Open RemoteConnect software
  • Create new project for SCADAPack 474
  • In Configuration-SPx70 Controller>SCADAPack x70 logic, open SCADAPack x70 logic editor
  • Under Project>Programs>Tasks>MAST, right click on MAST and select properties
  • MAST's properties window should appear
  • Change the configuration from Cyclic to Periodic, then click the Apply button and then the OK button to save the changes.
Mast
  • Make sure to apply update and build logic after writing the logic program

Schneider Electric New Zealand

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: