Search FAQs
What is error code '203' in iEm3100/iEM3200/iEm3300 series meters
Issue:
What is error code '203' in iEm3100/iEM3200/iEm3300 series meters
Product Line:
Acti9
Environment:
iEM3100/iEM3200/iEM3300
Resolution:
As per User Guide, error code 203 means the phase sequence reversed and it is mismatched with voltage and current.
Suggestions:
Please check voltage wiring (V1, V2, V3) to make sure that you have properly wired and still you are getting same error then interchanging the voltage wires of R-Phase and B-Phase and this should fix the issue.
What is error code '203' in iEm3100/iEM3200/iEm3300 series meters
Product Line:
Acti9
Environment:
iEM3100/iEM3200/iEM3300
Resolution:
As per User Guide, error code 203 means the phase sequence reversed and it is mismatched with voltage and current.
Suggestions:
Please check voltage wiring (V1, V2, V3) to make sure that you have properly wired and still you are getting same error then interchanging the voltage wires of R-Phase and B-Phase and this should fix the issue.
Released for:Schneider Electric New Zealand
Explore more
Range:
Explore more
Range: