Using the BMENOR2200 with DNP3 Group 12 Variation 1 binary output TCC command.
In order to use the BMENOR2200 Ethernet module with Group 12 Variation 1 binary output Trip Close Command, the DNP3 point must be configured as shown:
 
  • Configure the Trip Close mode.image.png
  • Configure the binary output point TCC for Trip_Close.a1



The format for the DNP3 Group 12 Variation 1 'Trip Close Command' select range specifier and object prefix sent by the device must be according to the following example:

a2




a3



a4


a5
 
 